Applications:
Provide lightning protection and over-voltage protection, can effectively ensure the safe operation of the power grid.
Features:
Surge arrester with a unique escape from the explosion-proof device (ejector arrester valve).
Can effectively prevent arrester valves from aging off moment, the ground to form a high voltage and external shield to form a pathway discharge.
Technical properties
Item |
AHY5WZ-10/27 |
AHY5WS-10/30 |
AHY5WS-13/36 |
AHY5WZ-17/45 |
AHY5WS-17/50 |
System Nominal Voltage(kV) |
6 |
6 |
10 |
15 |
15 |
Rated Voltage |
10 |
10 |
13 |
17 |
17 |
Continuous Operation Voltage (kV) |
8.0 |
8.0 |
10.4 |
13.6 |
13.6 |
Nominal Discharge Current(kA) |
5 |
5 |
5 |
5 |
5 |
Steep Current Impulse Residual Voltage (kV) |
≤31.0 |
≤34.6 |
≤41.3 |
≤51.8 |
≤57.5 |
Lightning Impulse Residual Voltage(kV) |
≤27.0 |
≤30.0 |
≤36.0 |
≤45.0 |
≤50.0 |
Switching Impulse Residual Voltage(kV) |
≤23.0 |
≤25.6 |
≤30.7 |
≤35 |
≤42.5 |
Long Duration Current Impulse withstand(A) |
150 |
75 |
150 |
150 |
100 |
High Current Impulse Withstand (kA) |
65 |
65 |
65 |
65 |
65 |
Item |
AHY5WZ-26/66 |
AHY5WZ-32/85 |
AHY5WZ-34/90 |
AHY5WS-34/85 |
System Nominal Voltage(kV) |
20 |
20 |
20 |
20 |
Rated Voltage |
26 |
32 |
34 |
34 |
Continuous Operation Voltage (kV) |
20.8 |
25.6 |
27.2 |
27.2 |
Nominal Discharge Current(kA) |
5 |
5 |
5 |
5 |
Steep Current Impulse Residual Voltage (kV) |
≤76 |
≤95 |
≤104 |
≤95 |
Lightning Impulse Residual Voltage(kV) |
≤66 |
≤30.0 |
≤90 |
≤85 |
Switching Impulse Residual Voltage(kV) |
≤56 |
≤75 |
≤80 |
≤75 |
Long Duration Current Impulse withstand(A) |
150 |
150 |
150 |
200 |
High Current Impulse Withstand (kA) |
65 |
65 |
65 |
65 |
Item |
AHY5WZ-51/134/400 |
AHY5WS-51/134/600 |
AHY5WZ-51/134/800 |
System Nominal Voltage(kV) |
35 |
35 |
35 |
Rated Voltage |
51 |
51 |
51 |
Continuous Operation Voltage (kV) |
40.8 |
40.8 |
40.8 |
Nominal Discharge Current(kA) |
5 |
5 |
5 |
Steep Current Impulse Residual Voltage (kV) |
≤154 |
≤154 |
≤154 |
Lightning Impulse Residual Voltage(kV) |
≤134 |
≤134 |
≤134 |
Switching Impulse Residual Voltage(kV) |
≤114 |
≤114 |
≤114 |
Long Duration Current Impulse withstand(A) |
400 |
600 |
800 |
High Current Impulse Withstand (kA) |
100 |
100 |
100 |