Application:
Petroleum, chemical industry, gas and power station and so on.
Key features:
• Adopt full digital control technology.
• Intelligent detection and monitoring function.
• Digitally control the static switch with zero switch.
• Full isolation between input and output.
• Super low output zero earth voltage.
• DC UPS isolated with utility power completely.
• Cubical design with power standard (customization).
• Multifunctional protection for over-voltage, under voltage, over current, short circuit and over temperature and so on.
• Large-screen LCD monitor with Chinese and English operation interface.
• Ultra-long 256 event record, user-friendly analysis and management to the situation of the power supply (touch screen display).
• Static bypass has a strong anti-overload capability.
Technical Parameters:
Model | 100KVA | 120KVA | ||
Capacity | 80KW | 96KW | ||
Input | ||||
Rated voltage | 380/400/415 Vac three-phase | |||
Voltage range | ±20% | |||
Frequency range | 50/60HZ±5% | |||
Power factor | ≥0.8 | |||
Current harmonic distortion | <5%with harmonic filter | |||
Soft Start | 0-100% in 10″ | |||
Bypass Input | ||||
Rated voltage | 380/400/415 Vac single-phase | |||
Permitted voltage range | ±15%(selectable from ±10% to±25% from front panel) | |||
Rated frequency | 50/60Hz | |||
Permitted frequency range | ±2%(selectable from ±1% to 5% from front panel) | |||
Standard features | BackFeed portection;split bypass line | |||
Batteries | ||||
Type | Maintenance-free lead-acid VRLA AGM/GEL;NICd | |||
Maximum recharge current(A) | 0.2 X C10 | |||
DC Voltage | 384VDC | 480VDC | ||
AC ripple voltage | <1% | |||
Inverter output | ||||
Number of phases | 3+N | |||
Rated voltage(V) | 380/400/415Vac | |||
Regulation of the output voltage | 348~424Vac phase/neutral(from control panel) | |||
Crest factor(Ipeak/Irms) | 3:1 | |||
Static stability | ±1% | |||
Dynamic stability | ±5% | |||
Frequency | 50/60Hz configurable | |||
Overload | 110% 125% 150% of the rated current for 5h/10’/1′ | |||
Frequency stability | ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present | |||
System | ||||
Remote signaling | Volt free contacts | |||
Remote controls | EPO and Bypass | |||
Communication | RS232+romote contacts | |||
Operation temperature | 0℃/+40℃ | |||
Relative humidity | <95% non condensing | |||
Colour | Light grey (RAL7035) | |||
Noise | 50-65dBA at 1m | |||
Protection degree | IP42 | |||
Efficiency Smart Mode | up to 98% | |||
Compliance | Safty: EN 62040-1-1(Directive 2006/95/EC);EMC:6200-2(Directive 2004/108/EC) | |||
Weight(KG)N.W | 770 | 855 |
Other Service
Service hours: 9:00am-19:00pm (China time)
Product service:
1. Pre-sales consultation; After-sales worry-free.
2. Support ODM and OEM.
3. Online guidance and Technical support.
Product Warranty:
One year warranty period against the B/L date 45 days later.(Possible to extend the warranty period to three years by add money)
FAQ:
We try to answer some frequently asked questions here, if these FAQs don't answer your questions, please refer to related information from our Product page: Documents Option, which contains Datasheet and Manual for you to download, or you can contact us directly.
What is an uninterruptible power supply system (UPS) and why do I need one?
An uninterruptible power supply (UPS) is an electrical device that provides emergency power to a load when the main power source (typically utility power) fails. It conditions incoming power to ensure clean and uninterrupted power, protects devices from power problems and enables seamless system shutdown during complete outages.
With aging electrical grids, rising power demand, severe weather, faulty wiring and disruptive devices connected to AC lines, equipment is under constant threat from power problems, making a UPS system an important investment. A UPS system is especially useful for networking equipment and other devices that can lose data when power is unexpectedly lost. With a wide range of cost-effective models available, a UPS system is an essential investment to prevent damage, data loss and downtime caused by power problems.
Phases of a UPS, such as a single-phase UPS or a three-phase UPS, describe the number of electrical phases that a UPS receives and transmits. Electrical utilities generate three-phase power because that is the most efficient way to transport electricity over long distances. And for larger power consumers, such as large data centers, industrial manufacturing and hospitals, the power stays as three-phase, requiring a three-phase UPS. For smaller power consumers, including residential or office buildings and most K-12 schools, the power is converted to single-phase power.
Some applications contain a mix of single-phase and three-phase equipment and require a UPS that can protect both. For those deployments, a split-phase UPS, which can simultaneously provide 120V and 208V output, is often the best option.
Do UPS systems offer surge and noise protection?