AGS series screw type water cooled water chiller designed with efficient silicon steel and special slots, and equipped with the inside and outside all around design to cool the flow channel so to ensure maximum efficiency of the compressor motor under any load.High efficiency double filtration oil separator ensures maximun heat exchage.Efficient, low noise and small vibration.
Screw Compressor Water Cooled Water Chiller AGS-240WDH
Specification
Model Item |
AGS-240WDH |
|
nominal cooling capacity |
kcal/h |
681120 |
kw |
875.8 |
|
input power |
kw |
176.6 |
max.runing current |
A |
468 |
power supply |
3PH 380V 50HZ |
|
refrigerant |
type |
R22/R407c/R410a/R134a |
kg |
168 |
|
type of control |
expansion valve |
|
compressor |
type |
sewi-hermetic screw |
88.3*2 |
||
start-up mode |
Y-△ |
|
capacity control(%) |
0-25-50-75-100 |
|
evaporator |
type |
Shell and tube |
chilled water flow(m3/h) |
136.2 |
|
6 |
||
condenser |
type |
shell and tube |
cooling water flow(m3/h) |
187 |
|
inlet and outlet pipe caliber(inch) |
4*2 |
|
safety protection |
compressor overheating protection, over-current protection, high and low pressure,over-temperature protection, flow switch, protection,phase sequence or missing phase protection, exhaust overheating protection |
|
weight |
kg |
3920 |
dimension |
mm |
4150*1320*2150 |
Note: 1.Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 17℃ Outlet chilled fluid temperature: 12℃
Inlet cooling water temperature: 30℃ Outlet cooling water temperature: 35℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
The temperature range of cooling water is from 18℃ to 37℃;
Temperature difference between inlet and outlet cooling water is from 3.5℃ to 10℃.
We reserve the right to modify the above dimensions or parameters without further notice.