Applications:
The Separable Connector establishes the connection between any polymeric insulated cable onto transformers, switchgears, motors or other equipment.
Features:
Technical properties
Standard |
IEC 60502 |
|||
Voltage classes |
6/10(12)kV |
8.7/15(17.5)kV |
12/20(24)kV |
18/30(36)kV |
Partial discharge test at ambient temperature |
10kV, <10pC |
15kV, <10pC |
20kV, <10pC |
30kV, <10pC |
AC withstand voltage test |
27kV 5min |
39kV 5min |
54kV 5min |
81kV 5min |
Impulse voltage withstand |
±75kV each polarity 10 times |
±95kV each polarity 10 times |
±125kV each polarity 10 times |
±170kV each polarity 10 times |
Selection table:
6/10(12)kV |
|||
Screen cable Connector |
Screen Rear cable Connector |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
AQ-12-630A-A |
AH-12-630A-A |
16.5mm-20.9mm |
70mm²--95mm² |
AQ-12-630A-B |
AH-12-630A-B |
20.3mm-24.3mm |
120-mm²--185mm² |
AQ-12-630A-C |
AH-12-630A-C |
24.7mm-29.5mm |
240mm²--300mm² |
AQ-12-630A-D |
AH-12-630A-D |
29.5mm-36.3mm |
400mm²--500mm² |
AQ-12-630A-E |
AH-12-630A-E |
34.5mm-41.5mm |
630mm² |
8.7/15(17.5)kV |
|||
Screen cable Connector |
Screen Rear cable Connector |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
AQ-17.5-630A-A |
AH-17.5-630A-A |
16.5mm-20.9mm |
25mm²--50mm² |
AQ-17.5-630A-B |
AH-17.5-630A-B |
20.3mm-24.3mm |
70mm²--120mm² |
AQ-17.5-630A-C |
AH-17.5-630A-C |
24.7mm-29.5mm |
150mm²--185mm² |
AQ-17.5-630A-D |
AH-17.5-630A-D |
29.5mm-36.3mm |
240mm²--400mm² |
AQ-17.5-630A-E |
AH-17.5-630A-E |
34.5mm-41.5mm |
500mm²--630mm² |
12/20(24)kV |
|||
Screen cable Connector |
Screen Rear cable Connector |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
AQ-24-630A-A |
AH-24-630A-A |
16.5mm-20.9mm |
35mm²--50mm² |
AQ-24-630A-B |
AH-24-630A-B |
20.3mm-24.3mm |
70mm²--95mm² |
AQ-24-630A-C |
AH-24-630A-C |
24.7mm-29.5mm |
120mm²--185mm² |
AQ-24-630A-D |
AH-24-630A-D |
29.5mm-36.3mm |
240mm²--300mm² |
AQ-24-630A-E |
AH-24-630A-E |
34.5mm-41.5mm |
400mm²-500mm² |
18/30(36)kV |
|||
Screen cable Connector |
Screen Rear cable Connector |
Cable Insulation OD(mm) |
Cable Conductor Cross-section(mm²) |
AQ-36-630A-A |
AH-36-630A-A |
25.2mm—30.2mm |
50mm²--95mm² |
AQ-36-630A-B |
AH-36-630A-B |
30.2mm—35.9mm |
120mm²--185mm² |
AQ-36-630A-C |
AH-36-630A-C |
35.9mm—41.2mm |
240mm²--300mm² |
AQ-36-630A-D |
AH-36-630A-D |
41.2mm--44.5mm |
400mm²--500mm² |
*NOTE:
1. Cable insulation outer diameter is one of the prerequisite for cable accessories selection.
2. For three-core cable, AQ/AH should be separately ordered.
3. The connector suit for bushings according to EN 50181, connection type C.