Specification
Model Item |
HBW-12 |
|
nominal cooling capacity |
kcal/h |
34400 |
kw |
40.00 |
|
input power |
kw |
9.62 |
power supply |
3PH 380V—460V 50HZ/60HZ |
|
refrigerant |
type |
R407C/R410A/R134A |
type of control |
expansion valve |
|
compressor |
type |
hermetic scroll type |
power(kw) |
8.12 |
|
condenser |
type |
shell and tube |
cooling water flow(m3/h) |
8.3 |
|
inlet/outlet pipe caliber(inch) |
2 |
|
evaporator |
type |
shell and tube+water tank |
chilled fluid flow(m3/h) |
6.9 |
|
volume(L) |
75 |
|
inlet and outlet pipe diameter(inch) |
2 |
|
pump |
power(kw) |
1.5 |
lift(m) |
20 |
|
safety protection |
compressor overheating protection, over-current protection, high and low pressure,over-temperature protection, flow switch, protection,phase sequence or missing phase protection, exhaust overheating protection |
|
weight |
kg |
500 |
dimension |
mm |
1320*710*1320 |
Note: 1.Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 17℃ Outlet chilled fluid temperature: 12℃
Inlet cooling water temperature: 30℃ Outlet cooling water temperature: 35℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
The temperature range of cooling water is from 18℃ to 37℃;
Temperature difference between inlet and outlet cooling water is from 3.5℃ to 10℃.
We reserve the right to modify the above dimensions or parameters without further notice.