HBC chiller use the world famous hermetic scroll type compressor,feature low noise,low vibration,low energy consumption and high efficiency.Environment-friendly R407C,R410A,R404A,R134A,etc,which is no harm to the ozone layer.Static plastic spray outer casing with simple structure and elegant appearance.
Industrial R410a Refrigerant Chiller China HBC-20(D)
Specification
Model Item |
HBC-20(D) |
|
nominal cooling capacity |
kcal/h |
51772 |
kw |
61 |
|
input power |
kw |
19.96 |
power supply |
3PH 380V 50HZ |
|
refrigerant |
type |
R134A/R407C/R410A |
type of control |
expansion valve |
|
compressor |
type |
hermetic scroll type |
power(kw) |
16.2 |
|
condenser |
type |
finned copper tube+low noise outer fan |
power(kw) |
1.56 |
|
cooling air flow(m3/h) |
20000 |
|
evaporator |
type |
shell and tube+water tank |
chilled fluid flow(m3/h) |
10.52 |
|
volume(L) |
170 |
|
inlet and outlet pipe diameter(inch) |
2 |
|
pump |
power(kw) |
2.2 |
lift(m) |
20 |
|
safety protection |
compressor overheating protection, over-current protection, high and low pressure,over-temperature protection, flow switch, protection,phase sequence or missing phase protection, exhaust overheating protection |
|
weight |
kg |
835 |
dimension |
mm |
2150*1130*1820 |
Note: 1.Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 17℃
Outlet chilled fluid temperature: 12℃
Inlet cooling air temperature: 30℃
Outlet cooling air temperature: 35℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
It is better to run the chiller while the ambient temperature at or below 35℃.
We reserve the right to modify the above dimensions or parameters without further notice.