Air-cooled chiller systems typically have a lower first and maintenance cost since they do not require a cooling tower, water pumps, and associated condenser water chemical treatment. In addition, we can accept OEM.
Scroll Type Compressor Air Cooled Chiller Unit ACK-60(F)
Specification
Model Item |
ACK-60(F) |
|
nominal cooling capacity |
kcal/h |
152048 |
kw |
184.8 |
|
input power |
kw |
57.48 |
power supply |
3PH 380V 50HZ |
|
refrigerant |
type |
R22(R134A/R407C/R410A) |
type of control |
expansion valve |
|
compressor |
type |
hermetic scroll type |
power(kw) |
49.8 |
|
condenser |
type |
finned copper tube+low noise outer fan |
power(kw) |
3.68 |
|
cooling air flow(m3/h) |
60000 |
|
evaporator |
type |
shell and tube+water tank |
chilled fluid flow(m3/h) |
31.86 |
|
volume(L) |
345 |
|
inlet and outlet pipe diameter(inch) |
3 |
|
pump |
power(kw) |
4 |
lift(m) |
23 |
|
safety protection |
compressor overheating protection, over-current protection, high and low pressure,over-temperature protection, flow switch, protection,phase sequence or missing phase protection, exhaust overheating protection |
|
weight |
kg |
1850 |
dimension |
mm |
2700*2200*2050 |
Note: 1.Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 17℃
Outlet chilled fluid temperature: 12℃
Inlet cooling air temperature: 30℃
Outlet cooling air temperature: 35℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
It is better to run the chiller while the ambient temperature at or below 35℃.
We reserve the right to modify the above dimensions or parameters without further notice.