IP56 floor outdoor UPS 1-10KVA with VRLA battery with cabinet air conditioner
IP56 floor outdoor UPS 1-10KVA with VRLA battery with cabinet air conditioner
Description
The CNW110 series communication side network outdoor UPS is a high-performance integrated outdoor online uninterruptible power supply system specially designed for outdoor microcellular base stations of wireless communication systems.
Application field
This UPS system is often used in urban corners, remote roads, mountainous areas, harsh environments such as high temperature (+50℃) or low temperature (-40℃), severe dust, humidity, rain, haze, and very poor power quality applications (The voltage is higher than 260V or lower than 160V for a long time, and the frequency changes abnormally)
Features
1. Using advanced DSP digital control technology, double conversion online design.
2. The enclosure protection grade is IP55.
3. With wide input voltage range and frequency.
4. Compatible with SNMP card for real-time remote monitoring.
5. Standard 19-inch rack-mounted UPS power modules are easy to install and maintain.
6. Compatible with VRLA batteries and Li-ion battery packs.
7. Different application scenarios can be pole mounted, wall mounted or floor mounted.
8. Integrated design of various protection functions.
9. You can reserve usage space for user equipment.
10. The cabinet can choose different materials.
Technical Parameters
Model | CNW110-1KVA | CNW110-2KVA | CNW110-3KVA | CNW110-6KVA | CNW110-10KVA |
Capacity | 1KVA/0.8KW | 2KVA/1.6KW | 3KVA/2.4KW | 6KVA/4.8KW | 10KVA/8KW |
Nominal voltage | 220/230/240VAC | ||||
Frequency | 50Hz/60Hz | ||||
Input | |||||
Voltage Range | 115-295VAC(±3VAC) | 176-297VAC(±3VAC) | |||
Frequency Range | 50Hz(46~54Hz); 60Hz(56~64Hz) | ||||
Soft Start | 0~100%5sec | ||||
Power factor | 0.98 | ||||
Output | |||||
Voltage Precision | 220/230/240VAC x (1±2%)VAC | ||||
Frequency Precision | 50Hz/60Hz±0.05Hz | ||||
Power Factor | 0.7/0.8(optional) standard 0.7 | ||||
Wave Distortion | Linear load<3% Non-linear load<6% | ||||
Overload capacity | Overload(110~150%)for 30 seconds, then automatically transfer to bypass. When load is normal, it can automatically transfer to normal mode. | ||||
Crest Factor | 3:1 | ||||
Transfer time | 0ms(AC to DC) | ||||
DC Supply Voltage | 36VDC | 96VDC | 96VDC | 240VDC | 240VDC |
Charging current | 4A/8A(optional) | 4A/8A(optional) | 4A/8A(optional) | 4.2A | 4.2A |
Internal Battery Capacity | (38/65/80/100AH)optional | ||||
Panel display | |||||
LED | Load level/Battery level, Battery indicator, Utility power, Inverter, Bypass, Overload, Fault | ||||
Communications | |||||
Communicate interface | RS232, SNMP card (optional) | ||||
Work Environment | |||||
Temperature | -40±℃-55℃ | ||||
Humidity | 0~95%(Non-condensing | ||||
Storage Temperature | -25℃~55℃ | ||||
Elevation | <1500m | ||||
Physical Characteristics | |||||
Net Weight(KG) | 85 | 125 | 125 | 150 | 150 |
Dimension: (W x D x H)mm |
613*640*954 | 650*753*1227 | 650*753*1227 | 940*940*1770 | 940*940*1770 |