AC-H series Heat and Cold Chillers, with dual-purpose for offering hot and cold water designed by ANGES, is widely used in sponge manufacturing, sauna and swimming pool, composite materials foam, medicine and chemical industries.
5 Ton Air Cooled Heat-cold Chiller Plant AC-5H
Specification
Model Item
AC-5H
nominal cooling capacity
kcal/h
12126
kw
14.1
input power
kw
14.13
power supply
3PH 380V 50HZ
refrigerant
type
R22(R134A/R407C/R410A)
type of control
capillary
compressor
type
hermetic scroll type
power(kw)
4
condenser
type
finned copper tube+low noise outer fan
power(kw)
0.38
cooling air flow(m3/h)
5000
evaporator
type
shell and tube+water tank
chilled fluid flow(m3/h)
2.43
volume(L)
60
inlet and outlet pipe diameter(inch)
1
pump
power(kw)
0.75
lift(m)
20
heating device
type
heating pipe
power(kw)
9
safety protection
compressor overheating protection, over-current protection, high and low pressure,over-temperature protection, flow switch, protection,phase sequence or missing phase protection, exhaust overheating protection
weight
kg
175
dimension
mm
1290*560*1250
Note: 1.Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 17℃
Outlet chilled fluid temperature: 12℃
Inlet cooling air temperature: 30℃
Outlet cooling air temperature: 35℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
It is better to run the chiller while the ambient temperature at or below 35℃.
We reserve the right to modify the above dimensions or parameters without further notice.