Water-cooled low temperature screw chiller is meticulous designed by ANGES Group, which owns many years of refrigeration experiences and adopts the advanced technology in the domestic and overseas.It mainly used in the Steel, Electronic, Pharmacy, Chemical, Food and other special Industry, the temperature can be adjust between -30 ℃ ~ 0 ℃.
-30℃~0℃ Water Cooled Low Temperature Chiller AGS-050WSL
Specification
Model Item |
AGS-050WSL |
|
nominal cooling capacity(kw) |
-10℃ |
94.1 |
-20℃ |
64.2 |
|
-30℃ |
40.1 |
|
power supply |
3PH 380V 50HZ |
|
input power |
kw |
45.4 |
compressor |
type |
Sewi hermetic screw |
45.4 |
||
refrigerant |
R22/R404A |
|
capacity control(%) |
33-66-100/25-50-75-100 |
|
start-up mode |
Y-△ |
|
evaporator |
type |
Shell and tube |
chilled fluid flow(m3/h) |
29.5 |
|
type |
shell and tube |
|
cooling water flow(m3/h) |
23.9 |
|
inlet and outlet pipe diameter |
evaporator(inch) |
3 |
condenser(inch) |
3 |
|
drain out port(inch) |
1 |
|
safety protection |
compressor overheating protection, over-current protection, high and low pressure,over-temperature protection, flow switch, protection,phase sequence or missing phase protection, exhaust overheating protection |
|
weight |
kg |
950 |
dimension |
mm |
2130*855*1540 |
Note: 1.Nominal cooling capacity calculated according to:
The chilled fluid is the 60% Ethylene Glycol aqueous solutions.
Inlet/outlet cooling water temperature:32℃/37℃.
2. Working condition:
The temperature range of chilled fluid is from -5℃ to -30℃;
Temperature difference between inlet and outlet chilled fluid is from 2.5℃ to 10℃.
The temperature range of cooling water is from 22℃ to 37℃;
Temperature difference between inlet and outlet cooling water is from 3.5℃ to 10℃.